MODEL
|
|
NIC2000 - 12
|
NIC2000 - 24
|
NIC2000 - 28
|
NIC2000 - 48
|
Output Voltage(Nominal)
|
V
|
12
|
24
|
28
|
48
|
Output Voltage Adjust Range By Trimmer
|
V
|
9.6 ~ 14.4
|
19.2 ~ 28.8
|
22.4 ~ 33.6
|
38.4 ~ 57.6
|
Max Output Current
|
A
|
105
|
82
|
71
|
42
|
Max Output Power
|
W
|
1260
|
1968
|
1988
|
2016
|
Temperature Coefficient
|
PPM/°C
|
100
|
Input Voltage/Freq.
|
---
|
171 ~ 265VAC continuous, 47 ~ 63Hz, Single phase (nominal: 230VAC)
|
Input Current (at 230 VAC)
|
A
|
≤10
|
Line Regulation
|
%
|
0.1% of full scale
|
Load Regulation (with remote sense connection)
|
%
|
0.5% of full scale (With Remote Sense Connection)
|
Ripple RMS, 5Hz ~ 1MHz
|
mV
|
25
|
40
|
40
|
50
|
Power Factor (Active PFC)
|
---
|
≥ 0.99 (at 230VAC & full load)
|
Efficiency (at 230VAC & Full load)
|
%
|
88
|
90.4
|
91
|
92
|
Inrush Current (at 230VAC)
|
A
|
≤ 40
|
Total Harmonic Distortion (THD)
|
%
|
< 5 (at 230VAC & Full load)
|
Hold-up Time
|
ms
|
10 (at 230 VAC & Full Load)
|
Over Current Protection
|
---
|
105% of Max. Output Current
|
Over Voltage Protection
|
---
|
120% of Adjusted Output Voltage
|
Remote Sense
|
---
|
Yes
|
Parallel Operation
|
---
|
Up to 4 Units
|
Output DC good
|
---
|
Yes
|
Remote Adjust
|
---
|
1 ~ 6V Program Voltage Input to Adjust Output 40 ~ 120% Of Nominal
|
Operating Temperature
|
°C
|
-35°C to +70°C (Derate linearly to 50% from +50°C to +70°C)
|
Storage Temperature
|
°C
|
-40°C To +85°C
|
Humidity(Non Condensing)
|
---
|
Operating:10 ~ 90%RH, Non Operating: 10 ~ 95%RH
|
Cooling
|
---
|
Internal variable speed fan
|
Weight
|
g
|
≤ 2000
|
Size(W×H×D)
|
mm
|
127×41×295
|